NSF2-3030 Intelligent Addressable Fire Alarm System
Features • Certified for seismic applications when used with the appropriate seismic mounting kit. • Approved for Marine applications when a marine-listed version is used with marine- listed compatible equipment. See DN-60688. • Complies with UL 2572 Mass Notification Systems (NFS2- 3030 version 20 or higher). • One to ten isolated intelligent Signaling Line Circuits (SLC) Style 4, 6 or 7. • Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-60820. • Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node. – Detectors can be any mix of ion, photo, thermal, or multisensor; wireless detectors are available for use with the FWSG. – Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay; wireless modules are available for use with the FWSG. • Large 16 line, 640 character LCD backlit display or use display-less as a network node. • Network options: – High-speed network for up to 200 nodes (NFS2-3030, NFS2- 640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NFS-3030, NFS- 640, and NCA). – Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS- 640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging. • Built-in Alarm, Trouble, Security, and Supervisory relays. • VeriFire® Tools online/offline program option